Title
43 Wellgate Dr
Accessory Structure (Sauna, Exercise Room & Hot Tub)
Submitted by Bridget Tipton, Studio Inlay
a) Staff notes this application received AHBR approval at the June 24, 2026 AHBR meeting. The applicant is requesting a modification of the approved plans that includes the enlargement of the proposed accessory structure and the addition of an exercise room.
b) Section III-1 (d)(3) of the Architectural Design Standards states that enclosed accessory buildings shall incorporate some elements similar to the main body, for example similar corner boards, window types, or materials. Question the proposed overall design and how it relates to the main mass.
c) Section III-1 (d)(3) of the Architectural Design Standards states that the roof of an enclosed accessory building should be the same roof shape as the roof of the main structure. Staff notes a flat roof is proposed, while the main mass as a hip roof.
d) Section III-1 (d)(3) of the Architectural Design Standards states that all facades (including the rear) over twelve (12) feet long shall have at least one window or door opening. Fenestration placement on the accessory structure shall be proportional to the house. Question if additional fenestration is needed on the front and rear elevations to better meet this requirement.
e) Verify proposed roofing material.